Duct Size Calculator
Enter your airflow and friction rate to get the round duct size, the matching rectangular sizes and the air velocity. Free, in US or metric units.
How to use ↓Built by a technician, for technicians.
Result
Duct Chart · Duct Size Calculator · ductchart.com
Estimates only: they can differ from your chart or the manufacturer's data by 5% or more (flex by 2 times or more), so verify accuracy for your own application against the design documents, manufacturer data and local code.
How to use
- Enter the airflow in CFM.
- Choose a friction rate (the default is 0.08 in. w.g. per 100 ft, 0.65 Pa/m) or a target velocity.
- Pick the duct type, then press Calculate.
- Read the exact and stock round size, the velocity and the rectangular sizes.
- Press Print result to take it to the job.
More calculators and charts
How the duct size calculator works
This free duct size calculator takes the airflow in CFM and a friction rate in inches of water gauge per 100 feet, and gives the round duct diameter that carries that airflow at that friction rate. It then moves to the next stock round size and shows the actual velocity and friction at that size, plus equal-friction rectangular sizes for common duct heights.
Friction is worked out with the Darcy-Weisbach equation and the Colebrook friction factor, solved exactly, for standard air (0.075 lb/ft³, about 70 °F at sea level). Galvanized sheet metal uses a roughness of 0.0005 ft. Fiberglass duct board and fully stretched flex both use 0.003 ft, and flex adds a compression multiplier. Rectangular sizes come from the Huebscher equal-friction equation used in ASHRAE Fundamentals.
Equal friction sizing is a quick way to size a branch or trunk once you know the friction rate. ACCA Manual D gets the design friction rate by taking the available static pressure times 100 and dividing by the total effective length of the longest run. The friction rate guide walks through it.
Use the round to rectangular converter for a specific height, the flex duct calculator to compare the published compression models, and the duct size chart to print a pocket chart. Used to a slide rule? How to use a ductulator walks one duct through every scale.
Results can differ from your duct chart or the manufacturer’s data by 5 percent or more, and flex by a factor of two or more. This is a sizing aid, not a substitute for a Manual D and J calculation or an engineer’s design.
FAQ
What friction rate should I use?
Many residential branch runs are designed around 0.08 to 0.10 in. w.g. per 100 ft (0.65 to 0.82 Pa/m), and 0.08 in. w.g. per 100 ft (0.65 Pa/m) is the default here. That is a common rule of thumb. Your design documents and the blower’s available static pressure decide it. See the friction rate guide.
Why does the stock size round up?
Rounding up never undersizes the duct. The velocity and friction shown are at the stock size you would actually install. Choose Nearest if you prefer the closest size, which can round down and push friction above your target.
Which duct type should I pick?
Sheet metal and duct board have different roughness, so the same friction rate gives a different diameter. For flex, pick the compression that matches how it will be installed. Fully stretched is the best case, and the design option uses 4% compression.
How accurate is it?
It is a calculation, not a measurement. Results can differ from your own duct chart or the manufacturer’s data by 5 percent or more, flex duct by a factor of two or more, and real ducts vary with joints, fittings and installation. Always follow the design documents, manufacturer data and local code.