CFM per Ton Calculator and Chart

Enter the tons and CFM per ton to get the total airflow. Split it across rooms if you need to.

How to use ↓

CFM per ton calculator

tons
Step 3 Split across rooms (optional)
Split by

Share (%)

Step 4 Calculate

How to use

  1. Enter the system size in tons.
  2. Leave CFM per ton at 400 or pick 350 or 450. You can type your own.
  3. To split the air, open Split across rooms and add a percentage or load for each room.
  4. Press Calculate, then use the Size link to size each branch.

Back to top ↑

Tons to CFM

Total airflow is the system size in tons times the CFM per ton. A 3 ton system at 400 CFM per ton moves 1,200 CFM. 350, 400 and 450 CFM per ton are a common rule of thumb, and 400 is the usual starting point, which is why it is the default here. It is a starting estimate, not design airflow: ACCA Manual D ties airflow to the sensible heat ratio and the equipment maker’s data. The CFM per ton guide explains the reasoning.

CFM per ton chart

This chart is the same sum done for common system sizes. Find the tonnage on the left and read across to the CFM per ton you are using. A 2.5 ton system at 400 CFM per ton is 1,000 CFM, and a 4 ton at 350 is 1,400 CFM. For a size that is not listed, use the calculator above.

Total CFM by system size and CFM per ton
Tons350 CFM/ton400 CFM/ton450 CFM/ton
1.5525600675
2700800900
2.58751,0001,125
31,0501,2001,350
3.51,2251,4001,575
41,4001,6001,800
51,7502,0002,250

Tons are the nominal size on the nameplate. The airflow the blower actually delivers depends on the speed tap and the static pressure it is working against, so check the manufacturer’s blower table for the real figure.

To split the air across rooms, enter a percentage for each room, or the room loads in Btu/h. With loads, each room gets the total airflow times its load divided by the total load, which is the Manual D method. Percentages that do not add to 100 are shared in proportion, and the calculator tells you.

A CFM calculator for each room

Used as a CFM calculator, it answers two questions: how much air the whole system should move, and how much each room gets. Once you have a room’s CFM, size its duct in the duct size calculator or read it off the duct size chart, and check the speed in the duct velocity calculator. If a branch will be flex, read it off the flex duct CFM chart instead, because flex carries less air than metal of the same size.

Each row has a Size link that opens the duct size calculator with that CFM filled in.

Example: a 3 ton system at 400 CFM per ton moves 1,200 CFM. With room loads of 12,000, 8,000 and 4,000 Btu/h, the rooms get 600, 400 and 200 CFM. Each of those goes straight into the duct size calculator.

FAQ

Is 400 CFM per ton right for my system?

It is the common figure and the default here. Common rule of thumb: 350 in humid climates and 450 or more in dry ones. Manual D ties airflow to the sensible heat ratio, so it is a starting estimate only. The equipment manufacturer’s blower table and design documents come first.

Do I split by percent or by load?

Use loads if you have a room by room load calculation. Use percentages if you are working from the design airflow for each room.

Why do the room CFM not add up exactly?

Each room is rounded to a whole CFM for display. The calculation itself is not rounded.