Flex duct CFM chart: how much air 6 to 16 inch flex carries

An 8 inch flex duct carries about 146 CFM at a friction rate of 0.10, as long as it's pulled out to within 4 percent of its full length. The same 8 inch in galvanized carries about 235. A 6 inch flex carries about 65 and a 10 inch about 284. Flex is rougher than sheet metal, and it loses more again when it's compressed, so a flex duct CFM chart reads well below a metal one.

Flex duct CFM chart at 4% compression

These figures are for flex at 4% compression, which is the design setting in the flex duct sizing calculator and the limit makers give for fully extended flex. They assume standard air (0.075 lb/ft³) in straight duct, using the LBNL compression model. Friction rates are in inches of water gauge per 100 feet. The last column is galvanized at 0.10, for comparison.

CFM carried by flex duct at 4% compression, with galvanized for comparison
Flex sizeCFM at 0.08CFM at 0.10Galvanized at 0.10
6 in.5865109
7 in.89100164
8 in.130146235
9 in.184207322
10 in.253284426
12 in.*411461693
14 in.*6196951,044
16 in.*8839911,488

* The lab data behind the compression model cover 6, 8 and 10 inch flex only. Above 10 inches the 10 inch value is held, so the 12 to 16 inch rows are an extrapolation. Treat them as rougher than the rest.

Estimates only: they can differ from your chart or the manufacturer's data by 5% or more (flex by 2 times or more), so verify accuracy for your own application against the design documents, manufacturer data and local code.

Read it like a metal chart. Find the flex size on the left, move across to the friction rate you're designing to, and that's the air the run can carry before it goes over that rate. Between 6 and 10 inches, flex at 4% carries roughly 60 to 67 percent of what the same size of galvanized carries.

If you'd rather start from the airflow, put the CFM and friction rate into the flex duct calculator. It gives the exact diameter and rounds it up to a stock flex size.

What compression does to it

The 4% chart assumes a good install. Here is the same flex at 0.10 fully stretched, at 4%, and at 15%. The 15% setting is the calculator's own label for a mediocre install, not a measured average, and flex that sags or gets squashed can be worse.

CFM carried by flex duct at 0.10 in. w.g. per 100 ft by compression
Flex sizeFully stretched4% compression15% compression
6 in.946541
8 in.20214695
10 in.367284193
12 in.*597461315
14 in.*898695475

Going from 4% to 15% takes an 8 inch run from about 146 CFM down to about 95. That's roughly a third of the air gone, from the same duct, just because it wasn't pulled tight. Even 4% isn't free: under the lab-based model it nearly doubles the friction of an 8 inch run compared with fully stretched flex.

That's why flex makers tell you to install it fully extended and support it at no more than 4 feet so it doesn't sag. The chart only holds if the install does.

Worked example: a 120 CFM bedroom run

Say a bedroom needs 120 CFM and the system is designed to 0.08. In galvanized, the duct size calculator puts that at 6.5 inches exact, so a 7. In flex at 4% it's 7.8 inches exact, so an 8. At 15% it's 8.9 inches, so a 9.

Here's what happens if the run goes in the wrong size:

Friction at 120 CFM for 7 and 8 in. galvanized and flex
Run at 120 CFMFriction (in. w.g. per 100 ft)
7 in. galvanized0.056
7 in. flex at 4%0.14
8 in. flex at 4%0.068
8 in. flex at 15%0.16

A 7 inch flex run at 120 CFM sits at about two and a half times the friction of 7 inch metal. Go up to an 8 and it drops back under 0.08, as long as the flex stays near stretched. Let that same 8 inch sag to 15% and it's at 0.16, about double the design rate.

In this example flex needed one size more than metal at 4%, and two more at 15%. Don't turn that into a rule. Look at the chart again: 8 inch flex at 4% carries less than 7 inch galvanized. Size flex from flex numbers every time.

If the run is going on a quote, quote the size you worked out, not the size that was there before. A bigger flex run is a line item, and it's easier to explain before the job than after it.

Why other flex charts show more air

Flex charts don't all agree, because there's more than one published way to account for compression. The Air Diffusion Council table puts no penalty on flex up to 4% compression. Run 8 inch flex at 4% through that model and it carries about 202 CFM at 0.10, the same as fully stretched. The LBNL model used here is fitted to lab measurements of compressed flex and gives about 146.

The ADC and ASHRAE models both come in under the LBNL lab data, by 23 to 55 percent in friction for 6 to 10 inch flex. That puts them on the unsafe side for sizing. The flex calculator shows all three side by side. If they give different stock sizes, take the larger one.

A chart like this isn't a substitute for a Manual D design or the manufacturer's data. It's for a quick check on a run you can see, or a sanity check on a number someone else gave you.

Frequently asked questions

How many CFM can a 6 inch flex duct carry?

About 58 CFM at 0.08 in. w.g. per 100 ft and about 65 CFM at 0.10, at 4% compression. Fully stretched it's about 94 at 0.10, and at 15% compression about 41. Galvanized of the same size carries about 109 at 0.10.

How many CFM does an 8 inch flex duct carry?

About 130 CFM at 0.08 and about 146 CFM at 0.10, at 4% compression. An 8 inch galvanized duct carries about 208 and 235 at the same rates.

Is there 11 inch flex duct?

Flex is stocked in whole inches from 3 to 10 inches and in even inches from 12 to 20, so there's no 11 inch stock size. The flex calculator rounds up to the next stock size for that reason.

Can I use a sheet metal CFM chart for flex?

No. It will overstate what the flex carries. At 0.10 an 8 inch galvanized duct carries about 235 CFM, and 8 inch flex at 4% compression about 146. Use flex figures, like the chart above or the flex duct calculator.