Duct Velocity Calculator

Enter the CFM and the duct size. Get the velocity, the friction rate and the velocity pressure.

How to use ↓

Duct velocity calculator

CFM
Step 2 Duct size
in.
Step 4 Calculate

How to use

  1. Enter the airflow in CFM.
  2. Choose round or rectangular and enter the size in inches.
  3. Pick the duct type. Friction depends on it.
  4. Press Calculate. Check the velocity note under the numbers.

Back to top ↑

Duct velocity, friction and velocity pressure

Velocity in fpm is the airflow in CFM divided by the cross-section area of the duct in square feet. For a rectangular duct the calculator uses the real area of the rectangle (the rectangular duct CFM chart lists common sizes). The friction rate uses the Darcy-Weisbach equation with the Colebrook friction factor for standard air, and for a rectangle it is worked out at the equal-friction round diameter.

Velocity pressure is the pressure of the moving air, from density times (velocity ÷ 1,097) squared, in inches of water gauge, with standard air at 0.075 lb/ft³. It is the number you use to size fitting losses and to read a pitot traverse.

The calculator flags two cases in plain words. Above about 1,200 fpm, noise and friction rise quickly, and published fitting equivalent lengths are less reliable at that speed. Below about 400 fpm the duct may be bigger than it needs to be, which is a common rule of thumb rather than a limit.

If the velocity is not where you want it, go back to the duct size calculator and size by target velocity, or look it up on the duct size chart. If the whole system feels tight, a total external static pressure test shows whether the supply or return side is the problem.

Example: 400 CFM in a 12 in. round duct moves 509 fpm, with 0.036 in. w.g. per 100 ft of friction. Push 1,000 CFM through a 10 in. round and the velocity is 1,833 fpm, so the page flags it.

Fabric duct velocity

For fabric (sock) duct, enter the CFM and the round inlet size to get the inlet velocity in fpm, which is the same math as any round duct. The friction and fitting numbers here are for sheet metal and flex, so they do not describe air leaving through porous fabric or vents along its length.

Fabric duct is sized on inlet velocity, and the makers publish their own figures:

Limits differ by maker, fabric and product line, so check the selection against the data for the duct you are buying. Example: 3,000 CFM into a 20 in. inlet runs at about 1,375 fpm, under the DuctSox figure for runs with fittings.

FAQ

What velocity is too high?

It depends on the job. Above about 1,200 fpm noise and friction climb quickly, so this page flags it. Design documents and the room’s noise needs come first.

Why is the rectangular friction at the equivalent round?

Equal friction at equal airflow is how an equivalent round diameter is defined, so the friction rate of a rectangle is the friction of its equivalent round.

Does velocity change with duct type?

No. Velocity depends only on airflow and area. Friction changes with the roughness of the duct type.

What velocity should fabric duct run at?

Use the maker’s figure. DuctSox sizes straight runs at 1,600 fpm, runs with fittings at 1,400 fpm and quiet spaces at 1,000 fpm. Prihoda recommends under 8.0 m/s, and 2.0 to 4.0 m/s for quiet spaces.