HVAC Duct Size Chart

Round duct diameter and velocity for 25 to 5,000 CFM at four friction rates, with rectangular equivalents.

How to use ↓

Duct size chart

Round duct, galvanized sheet metal, standard air

ductchart.com

Round diameter and velocity by airflow

Round duct diameter and velocity by airflow at four friction rates, galvanized sheet metal
CFM0.05 in. w.g./100 ft0.08 in. w.g./100 ft0.10 in. w.g./100 ft0.15 in. w.g./100 ft
Dia in.fpmDia in.fpmDia in.fpmDia in.fpm
254.02843.63453.53783.2446
505.23414.74134.54534.1534
756.03795.54595.25034.8593
1006.74086.14945.85415.4638
1507.84537.15486.86016.2708
2008.74877.95907.56466.9761
2509.45168.66248.26847.5805
30010.15409.26548.87168.1843
40011.258110.27039.87699.0906
50012.261411.174310.68139.8958
60013.164311.977811.485110.51,002
80014.669113.283612.791411.71,076
1,00015.873014.488313.896612.71,137
1,20017.076415.492414.81,01113.61,190
1,50018.580816.897616.01,06814.81,257
2,00020.686718.71,04817.91,14616.51,348
2,50022.491620.41,10719.51,21017.91,424
3,00024.095821.81,15720.81,26519.21,488
4,00026.71,02724.31,24123.21,35721.41,596
5,00029.11,08526.51,31025.31,43323.31,684

Rectangular equivalents (equal friction)

Rectangular sizes equal to each round diameter: width for each height
Round in.Width (in.) for a height of
4 in.6 in.8 in.10 in.12 in.14 in.
44322*2*2*
5643332*
6864433*
71176544
815107655
920*129766
1026*1511987
1240*231613119
1459*33*22171412
1683*45*30231916
18113*60*40*302420
20148*78*51*373025
24239*125*80*58*4537

* Aspect ratio over 4:1. Widths are rounded up to the next whole inch (in mm: up to the next whole mm). Round diameters are exact, not rounded to stock sizes. Velocity is at that diameter.

Calculated at build time from the equations, not copied from another chart: Darcy-Weisbach friction with the Colebrook friction factor (ASHRAE Duct Systems Design Guide), galvanized roughness 0.0005 ft, standard air 0.075 lb/ft³. Rectangular sizes by the Huebscher equal-friction equation (ASHRAE Fundamentals). Estimates only: they can differ from your chart or the manufacturer's data by 5% or more (flex by 2 times or more), so verify accuracy for your own application against the design documents, manufacturer data and local code.

Need an exact size? Use the calculator →

How to use

  1. Find your CFM down the left side.
  2. Read across to your friction rate. The first number is the round diameter in inches, the second is the velocity in fpm.
  3. For a rectangular duct, find the round size in the second table and read the width under your height.
  4. Press Print chart. It prints on one page, Letter or A4.

Back to top ↑

About this duct size chart

This duct sizing chart lists the round diameter that carries each airflow at friction rates of 0.05, 0.08, 0.10 and 0.15 in. w.g. per 100 ft, for galvanized sheet metal, along with the velocity in that diameter. Diameters are exact, so round up to the next stock size on the job. For anything between the rows, or for duct board and flex, use the duct size calculator.

The numbers are generated from the same equations as the calculator: Darcy-Weisbach with the Colebrook friction factor, galvanized roughness 0.0005 ft and standard air. They are not copied from a printed chart, so they can differ a little from the ductulator in your truck. (If you want a refresher on reading one, see how to use a ductulator.) Results can differ from another chart by 5 percent or more either way.

The second table gives equal-friction rectangular sizes. Pick the height your space allows and read off the width, rounded up to a whole inch. An asterisk marks sizes over 4:1, which cost more sheet metal and tend to leak and make noise. For the CFM a rectangle carries, see the rectangular duct CFM chart. For another height or the reverse conversion, use the round to rectangular converter.

Reading it as a round duct CFM chart

For a size-by-size table, see the CFM chart for round duct. To go the other way, from a duct you already have to the CFM it carries, find the diameter in your friction-rate column and read the CFM on the left. If your size sits between two rows, the airflow is between those rows too.

Using it for HVAC ductwork sizing

Start from the airflow each run needs: the total from the CFM per ton calculator, split by room. Pick a friction rate from the available static pressure and the total effective length (the friction rate guide shows how), then read the size for each run. Check the velocity column against the space; supply branches near bedrooms need lower speeds than a trunk in a mechanical room.

Example: 400 CFM at 0.08 in. w.g. per 100 ft needs a 10.2 in. round duct, moving 703 fpm. The next stock size is 12 in. For a rectangular run with an 8 in. height, the second table gives an 11 in. width.

FAQ

Which friction rate does the chart use?

It shows four: 0.05, 0.08, 0.10 and 0.15 in. w.g. per 100 ft. Lower rates give bigger, quieter ducts. See the friction rate guide for how to choose.

Is the rectangular size the same speed as the round?

No. The equivalent size matches friction at the same airflow, not velocity. The rectangle has more area, so the air moves slower than in the round duct.

Does the chart work for flex or duct board?

No, it is for galvanized sheet metal. Duct board and flex are rougher, so they need a bigger diameter for the same friction rate. Use the flex duct calculator or the main calculator.

Can I read it as a round duct CFM chart?

Yes. Find your duct diameter in the column for your friction rate and read the CFM on the left.