A 10 inch round galvanized duct carries about 426 CFM at a friction rate of 0.10, and about 378 CFM at 0.08. A 6 inch carries 109 at 0.10. A 16 inch carries 1,488. Those are the numbers people mean when they search for a CFM chart for duct: you already know the size, and you want to know the air.
Most duct charts are built the other way round. You start with the airflow and read off a diameter. That's fine on a new design. On an existing house the duct is already in the ceiling, and the useful question is how much it can move.
CFM by round duct size
Galvanized sheet metal, standard air (0.075 lb/ft³), straight duct. Friction rates are in inches of water gauge per 100 feet.
| Round size | CFM at 0.08 | CFM at 0.10 |
|---|---|---|
| 4 in. | 32 | 36 |
| 5 in. | 59 | 66 |
| 6 in. | 96 | 109 |
| 7 in. | 145 | 164 |
| 8 in. | 208 | 235 |
| 9 in. | 285 | 322 |
| 10 in. | 378 | 426 |
| 12 in. | 615 | 693 |
| 14 in. | 926 | 1,044 |
| 16 in. | 1,321 | 1,488 |
| 18 in. | 1,806 | 2,033 |
| 20 in. | 2,387 | 2,688 |
Estimates only: they can differ from your chart or the manufacturer's data by 5% or more (flex by 2 times or more), so verify accuracy for your own application against the design documents, manufacturer data and local code.
Read it like this. Find the duct you've got in the left column. Move across to the friction rate you're designing to. That number is the airflow the duct can carry before it goes over that rate. Push more air through and it still works, it just costs more static pressure and moves faster.
Notice how fast capacity climbs with size. Going from 8 to 10 inches adds more than 80 percent at either rate. Going from 14 to 16 adds over 400 CFM at 0.10. One stock size is a big step, in both directions.
Worked example: a bigger system on old ductwork
Say a house has a 3 ton system on a 16 inch round supply trunk, and the customer wants to go to 4 tons. Using 400 CFM per ton, which is the site's default and a common rule of thumb rather than a requirement, that's 1,200 CFM now and 1,600 CFM after.
Look up 16 inches on the chart. At 0.10 it carries 1,488 CFM. So it handles the 1,200 with room to spare, and it comes up short at 1,600.
Here's what that looks like in numbers:
| Duct and airflow | Friction (in. w.g. per 100 ft) | Velocity |
|---|---|---|
| 16 in. at 1,200 CFM (3 tons) | 0.067 | 859 fpm |
| 16 in. at 1,600 CFM (4 tons) | 0.11 | 1,146 fpm |
| 18 in. at 1,600 CFM (4 tons) | 0.064 | 905 fpm |
The same 16 inch trunk goes from comfortably under 0.10 to over it, and the air speeds up by about a third. The duct size calculator puts 1,600 CFM at 0.10 at 16.4 inches exact, and rounds that up to an 18.
Whether 0.11 is acceptable depends on the static pressure you have to spend and how long the run is, so I wouldn't call it on the trunk alone. The friction rate guide shows how to work out what the system can afford. And the trunk is only one duct. Every branch off it gets the same check with its own airflow. For the real design, ACCA Manual D governs, not this chart.
What I would do is run this check before the quote goes out, not after the install. If the trunk needs to go up a size, that's a ductwork line on the quote, and the customer hears about it up front.
Flex reads differently
Everything above is galvanized. Flex is rougher, and compression makes it worse. At 0.10, an 8 inch galvanized duct carries about 235 CFM. The same 8 inch in flex at the flex duct calculator's design setting (4% compression) carries about 146. Don't read a flex run off a sheet metal chart. You'll overestimate it. Use the flex duct CFM chart instead. For sheet metal rectangles, there's a rectangular duct CFM chart too.
Frequently asked questions
How many CFM can a 6 inch round duct carry?
About 96 CFM at 0.08 in. w.g. per 100 ft and about 109 CFM at 0.10, for galvanized sheet metal. Flex of the same size carries less. These are estimates; check them against your design.
How many CFM does a 10 inch round duct carry?
About 378 CFM at 0.08 and about 426 CFM at 0.10, galvanized. At 400 CFM a 10 inch runs about 0.089 of friction and 733 fpm.
How do I read a CFM chart for round duct?
Find your duct diameter, then read across to the friction rate you're designing to. The number there is the airflow that duct carries at that rate. The printable duct size chart works the same way in reverse: find the diameter in your friction-rate column and read the CFM on the left.
Can I put more CFM through a duct than the chart shows?
The air will still flow, but the friction and the velocity both go up. A 16 inch round at 1,600 CFM runs about 0.11 of friction and 1,146 fpm, against 0.067 and 859 fpm at 1,200 CFM. Whether that's acceptable depends on the static pressure the system has to spend.