Round up to the next stock size unless you have a reason not to. A duct sizing chart gives you the exact diameter for your airflow and friction rate, like 10.2 inches for 400 CFM at 0.08. Nobody sells 10.2. Going up keeps you at or under the friction rate you designed for. Going down puts you over it, and sometimes by more than you'd guess.
Exact size vs stock size
Here are some common airflows at the two friction rates people use most, with the exact diameter and the stock size the duct size calculator picks when it rounds up. Galvanized round duct, standard air (0.075 lb/ft³).
| Airflow | Exact at 0.08 | Stock | Exact at 0.10 | Stock |
|---|---|---|---|---|
| 100 CFM | 6.1 in. | 7 in. | 5.8 in. | 6 in. |
| 200 CFM | 7.9 in. | 8 in. | 7.5 in. | 8 in. |
| 400 CFM | 10.2 in. | 12 in. | 9.8 in. | 10 in. |
| 600 CFM | 11.9 in. | 12 in. | 11.4 in. | 12 in. |
| 800 CFM | 13.2 in. | 14 in. | 12.7 in. | 14 in. |
| 1,000 CFM | 14.4 in. | 16 in. | 13.8 in. | 14 in. |
| 1,200 CFM | 15.4 in. | 16 in. | 14.8 in. | 16 in. |
Estimates only: they can differ from your chart or the manufacturer's data by 5% or more (flex by 2 times or more), so verify accuracy for your own application against the design documents, manufacturer data and local code.
Some of those are close. 600 CFM at 0.08 wants 11.9 inches, and a 12 is basically a perfect fit. Others aren't. 400 CFM at 0.08 jumps from 10.2 all the way to 12, because the calculator's stock list has no 11.
That list is an assumption, and it's worth knowing what it is. The calculator treats round pipe as stocked in every inch from 3 to 10, then even sizes from 12 up. What's actually on the shelf depends on your distributor, and a sheet metal shop can make an 11 to order. If you can get one, it's worth pricing, and the next table shows why.
What rounding does at 400 CFM
The design was 0.08 inches of water gauge per 100 feet. Here's what each real size gives you:
| Round size | Friction (in. w.g. per 100 ft) | Velocity |
|---|---|---|
| 10 in. (rounded down) | 0.089 | 733 fpm |
| 11 in. (if you can get it) | 0.056 | 606 fpm |
| 12 in. (next stock size up) | 0.036 | 509 fpm |
Dropping to 10 puts you about 11 percent over the design rate. On a short branch I'd probably live with that. The 12 goes the other way and uses less than half the friction you planned for. It costs more pipe and more space, and the air moves slower, but it won't be the duct that starves a room.
Look at 1,000 CFM at 0.08 too. The exact size is 14.4 inches and the next stock size is 16. A 14 gives you 0.092 of friction and 935 fpm. A 16 gives 0.048 and 716 fpm. A 15, if a shop makes it, sits in between at 0.066 and 815 fpm. Same story as the 400 CFM run: the gap between stock sizes decides more than the chart does.
When I'd round down
This is a judgment call, not a rule. I'd round down when the exact size is only a little over a stock size and the run is short with few fittings. The friction you end up with also has to fit the static pressure you worked out for the system. Going from 9.8 to 10 inches at 0.10 is no decision at all. Going from 10.2 to 10 at 0.08 is a small one. Going from 14.4 to 14 on a trunk carrying 1,000 CFM is one I'd want to check against the whole system first, because every room downstream lives with it.
If you aren't sure what friction rate you have to spend, start with the friction rate guide. The rounding question only makes sense once that number is real. And for the full design, ACCA Manual D governs, not a chart.
One more thing. Everything above is galvanized sheet metal. Flex is rougher and needs a bigger diameter for the same airflow, so read flex sizes from the flex duct calculator or the flex duct CFM chart instead.
And if the paperwork after the install is what slows you down, I put together a comparison of the best field service software for small trade businesses.
Frequently asked questions
Should I round a duct size up or down?
Up, by default. Rounding up keeps the friction at or below your design rate. Round down only when the exact size is just over a stock size and the higher friction still fits your available static pressure.
Why does the calculator jump from 10 inches to 12?
Its stock list goes 3 to 10 inches in 1-inch steps, then even sizes from 12. Stock depends on your distributor. If you can get an 11, it can be a closer fit. At 400 CFM it runs about 0.056 of friction, between the 10 and the 12.
Can I use the calculator's nearest-size setting instead?
Yes. The duct size calculator lets you pick next size up or nearest. Nearest will sometimes round down. The result shows the friction and velocity at the stock size it picked, so check those before you use it.