A 12 x 8 inch rectangular galvanized duct carries about 505 CFM at a friction rate of 0.10, and about 448 CFM at 0.08. A 20 x 8 carries about 944 at 0.10. A 24 x 12 carries about 2,118. The full chart is below, for 18 common sizes.
For a size that isn't on the list, put it into the round to rectangular converter. It gives the round duct with the same friction, and that round size tells you the airflow.
CFM by rectangular duct size
Galvanized sheet metal, standard air (0.075 lb/ft³), straight duct. Width comes first, then height. Friction rates are in inches of water gauge per 100 feet. The velocity column is the air speed inside the rectangle at the 0.10 airflow.
| Size (in.) | Round equivalent | CFM at 0.08 | CFM at 0.10 | Velocity at 0.10 |
|---|---|---|---|---|
| 8 x 6 | 7.6 in. | 178 | 201 | 604 fpm |
| 10 x 6 | 8.4 in. | 237 | 268 | 642 fpm |
| 12 x 6 | 9.1 in. | 297 | 335 | 671 fpm |
| 14 x 6 | 9.8 in. | 358 | 404 | 693 fpm |
| 10 x 8 | 9.8 in. | 354 | 400 | 720 fpm |
| 12 x 8 | 10.7 in. | 448 | 505 | 758 fpm |
| 14 x 8 | 11.5 in. | 543 | 613 | 788 fpm |
| 16 x 8 | 12.2 in. | 640 | 722 | 812 fpm |
| 20 x 8 | 13.5 in. | 838 | 944 | 850 fpm |
| 24 x 8 | 14.6 in. | 1,038 | 1,170 | 877 fpm |
| 12 x 10 | 12.0 in. | 610 | 687 | 825 fpm |
| 14 x 10 | 12.9 in. | 743 | 838 | 862 fpm |
| 16 x 10 | 13.7 in. | 880 | 992 | 893 fpm |
| 20 x 10 | 15.2 in. | 1,160 | 1,306 | 941 fpm |
| 24 x 10 | 16.5 in. | 1,444 | 1,627 | 976 fpm |
| 16 x 12 | 15.1 in. | 1,134 | 1,278 | 959 fpm |
| 20 x 12 | 16.8 in. | 1,503 | 1,693 | 1,016 fpm |
| 24 x 12 | 18.3 in. | 1,881 | 2,118 | 1,059 fpm |
Estimates only: they can differ from your chart or the manufacturer's data by 5% or more (flex by 2 times or more), so verify accuracy for your own application against the design documents, manufacturer data and local code.
Find the duct you have in the left column and read across to your friction rate. That number is the airflow the duct carries before it goes over that rate. More air will still go through it. It just costs more static pressure and moves faster.
Where the numbers come from
Each rectangle is turned into the round duct that has the same friction at the same airflow. That's the equal-friction equivalent diameter, 1.30 × (a × b)0.625 ÷ (a + b)0.25, the same formula the converter uses. The round size then goes through the same friction equations as the duct size chart.
So a 12 x 8 behaves like a 10.7 inch round for pressure drop. The air moves slower in the rectangle, though. It has 96 square inches of opening against about 89 for the round, so at 505 CFM the rectangle runs 758 fpm while its round twin runs about 815. If you're checking noise near a register, look at the velocity column, not the round size.
Flat ducts carry less air
Two ducts with the same opening area don't carry the same air. The flatter one has more wall for the air to rub against.
| Size (in.) | Area | Aspect ratio | CFM at 0.10 |
|---|---|---|---|
| 10 x 10 | 100 sq in. | 1:1 | 541 |
| 12 x 8 | 96 sq in. | 1.5:1 | 505 |
| 16 x 6 | 96 sq in. | 2.7:1 | 474 |
The 12 x 8 and the 16 x 6 have exactly the same area, and the 16 x 6 carries about 6 percent less. Squash the same 96 square inches into a 24 x 4 and it drops to about 404 CFM. That's a 6:1 duct, well past the 4:1 point where the converter starts warning about extra sheet metal, leakage and noise. When a joist bay forces a shallow duct, expect to give up some airflow and go wider to get it back.
Worked example: a 20 x 8 trunk and a bigger system
Say a house has a 20 x 8 supply trunk and the customer wants a 3 ton system. Using 400 CFM per ton, which is the site's default and a common rule of thumb rather than a requirement, that's 1,200 CFM.
The chart puts a 20 x 8 at about 944 CFM at 0.10, so it comes up short. Push 1,200 CFM through it and the friction rate is about 0.16, with the air moving at 1,080 fpm in the rectangle.
To carry 1,200 CFM at 0.10 you need about a 14.8 inch round. The converter turns that into these rectangles, with the width rounded up to a whole inch:
| Height you can fit | Size (in.) | Aspect ratio | Velocity at 1,200 CFM |
|---|---|---|---|
| 8 in. | 25 x 8 | 3.1:1 | 864 fpm |
| 10 in. | 19 x 10 | 1.9:1 | 909 fpm |
| 12 in. | 16 x 12 | 1.3:1 | 900 fpm |
If the space only allows 8 inches, the trunk needs to go about 5 inches wider. That's worth knowing before the quote goes out, because it turns a swap into a ductwork job. Whether 0.16 could work on this house depends on the static pressure the system has to spend and how long the run is, and the friction rate guide shows how to work that out. The trunk is also only one duct. Every branch gets its own check, and for the real design ACCA Manual D governs, not this chart.
Swapping a round duct for a rectangle
A common mistake is to treat a 12 x 8 as a straight swap for a 10 inch round. It's bigger than that. At 400 CFM a 10 inch round runs about 0.089 of friction and 733 fpm. A 12 x 8 at the same 400 CFM runs about 0.065 and 600 fpm, because it matches a 10.7 inch round. That's fine if you want the extra room, but it's not the same duct.
Going the other way is where people get caught. Matching the area gives a rectangle that looks right on paper and carries less than the round it replaced. A 12 x 6.5 has about the same area as a 10 inch round (78 square inches against 78.5), but it only matches a 9.5 inch round for friction. The hydraulic diameter, 2ab ÷ (a + b), goes wrong in the other direction: it calls a 12 x 8 a 9.6 inch duct when it behaves like a 10.7. Use the equivalent diameter, which is what the converter and this chart both do. To go from airflow to a round size first, use the duct size calculator, or read sizes the other way in the CFM chart for round duct.
This chart is for galvanized sheet metal only. Duct board is rougher, so the same size carries less air at the same friction rate, and flex is rougher again once it's compressed. Don't read either one off this table.
Frequently asked questions
How many CFM can a 12 x 8 duct carry?
About 448 CFM at 0.08 in. w.g. per 100 ft and about 505 CFM at 0.10, for galvanized sheet metal. It has the same friction as a 10.7 inch round. These are estimates; check them against your design.
How many CFM does a 20 x 8 duct carry?
About 838 CFM at 0.08 and about 944 CFM at 0.10, galvanized. At 1,200 CFM the same duct runs about 0.16 of friction and 1,080 fpm.
How do I read a rectangular duct CFM chart?
Find the width and height of your duct, then read across to the friction rate you're designing to. The number there is the airflow that size carries at that rate. For a size that isn't listed, convert it to its round equivalent and read the round size instead.
Is a rectangular duct the same as a round duct with the same area?
No. A rectangle has more wall for the air to rub against, so it carries less than a round duct of the same area. A 12 x 8 has 96 square inches but matches a 10.7 inch round, which has about 89. Compare ducts by equivalent diameter, not area.