How to use a ductulator (slide rule or online)

A ductulator links four numbers: airflow in CFM, friction rate, round duct diameter and air velocity. Set any two and it shows you the other two. For sizing a duct, the two you set are the airflow and the friction rate. Line 800 CFM up against 0.08 on the galvanized side and you get a round duct of about 13.2 inches, moving air at about 836 fpm. You can't buy a 13.2, so you go up to a 14, and at that size the air slows to about 748 fpm.

That's the whole method. The rest of this page is about doing each step with numbers you can defend, and reading the back of the wheel without shrinking the duct by accident.

If you don't have the cardboard wheel on you, the duct size calculator on this site works as an online ductulator. Type in the CFM and a friction rate (or a target velocity) and it gives the exact size, the next stock size, the velocity at that size and the rectangular equivalents in one go.

What the scales mean

Airflow is the air the duct has to carry. For a branch that's the room's share of the blower CFM. For a trunk it's everything downstream of that point.

Friction rate is the pressure the duct uses up for every 100 feet of straight run, in inches of water gauge. A lower rate gives a bigger duct and slower air. A higher rate gives a smaller duct, faster air and more static pressure spent.

Diameter is the inside size of a round duct, and velocity is the airflow divided by the duct's cross-section area, in feet per minute. Most wheels also have a rectangular scale on the back that lists sizes carrying the same air at the same friction as a given round.

Step by step: sizing an 800 CFM trunk

Here's one duct taken all the way through, galvanized sheet metal, standard air (0.075 lb/ft³). Every number comes from the same engine the calculator uses.

  1. Get the airflow. Say it's a 2 ton system and you're using 400 CFM per ton. That's 800 CFM on the trunk. The 400 figure is a common rule of thumb and the site's default, not a requirement. The CFM per ton calculator works it out and splits it by room.
  2. Set the friction rate. Don't just pick one. Manual D takes the static pressure left over for the ducts, times 100, divided by the total effective length of the longest run. With 0.12 in. w.g. left and a 150 foot effective run, that's 0.12 × 100 ÷ 150 = 0.08. Those numbers are an illustration, so use your own job's. The friction rate guide walks through where each one comes from.
  3. Line up the airflow with the friction rate. On the wheel, put 800 CFM against 0.08. Read the round size in its window: about 13.2 inches.
  4. Read the velocity at the same setting. About 836 fpm in that exact 13.2 inch duct.
  5. Pick a size you can actually buy. The calculator's stock list runs every inch from 3 to 10, then even sizes from 12, so 13.2 goes up to 14. In a 14 inch round, 800 CFM runs about 0.061 of friction at 748 fpm. Going down to 12 would put it at about 0.131 and 1,019 fpm, well over the 0.08 you planned. Rounding duct sizes covers when going down is worth it.

The velocity is the check, not the target. The calculator flags anything above about 1,200 fpm, where noise and friction climb quickly. It also notes anything under about 400 fpm, which may be bigger than it needs to be (a rule of thumb, not a limit). 748 fpm sits comfortably between the two.

Reading the rectangular side

Turn the wheel over when the round won't fit the joist bay. For the same 800 CFM at 0.08, here are the equal-friction rectangles for each duct height, worked from the exact 13.2 inch round with the width rounded up to a whole inch:

Rectangular duct sizes equal in friction to a 13.2 in. round at 800 CFM and 0.08 in. w.g. per 100 ft
HeightWidthAspect ratioVelocity
4 in.51 in.12.8 : 1 (too flat)565 fpm
6 in.29 in.4.8 : 1 (too flat)662 fpm
8 in.20 in.2.5 : 1720 fpm
10 in.15 in.1.5 : 1768 fpm
12 in.13 in.1.1 : 1738 fpm
14 in.11 in.1.3 : 1748 fpm

Estimates only: they can differ from your chart or the manufacturer's data by 5% or more (flex by 2 times or more), so verify accuracy for your own application against the design documents, manufacturer data and local code.

The calculator flags any shape flatter than 4 to 1. Keep the aspect ratio at 4:1 or less when you can, and as close to square as the space allows. So an 8 x 20 or a 10 x 15 is the realistic pick here, depending on the space. The round to rectangular converter does the same thing for any height you type in.

Sizing by velocity instead

Most wheels and the calculator also let you set a target velocity in place of the friction rate. Put in 800 CFM at 900 fpm (a number picked for this example, not a recommendation) and you get an exact size of about 12.8 inches. Then look at what that duct costs you in friction: about 0.096 per 100 feet. That's above the 0.08 the system could afford in the example above.

That's the problem with sizing on speed alone. A velocity tells you nothing about whether the duct fits the static pressure you have to spend. Set the friction rate from the job first, then use the velocity to catch a duct that's going to be noisy.

Readings that shrink the duct

The first is matching area instead of using the rectangular scale. A 13.2 inch round has about 138 square inches of area. Divide by an 8 inch height and you'd get 17.2, so 8 x 18. But an 8 x 18 only has an equivalent round of about 12.9 inches, and at 800 CFM it runs about 0.093 of friction, roughly 16 percent over the design rate. The equal-friction answer is 8 x 20, at about 0.073. Rectangles have more wall for the same area, and the wall is where the friction comes from.

Reading flex or duct board off the galvanized side. Rougher duct needs a bigger diameter for the same air. At 800 CFM and 0.08, galvanized wants 13.2 inches exact, fiberglass duct board wants 14.0, and flex at the calculator's design setting (4% compression) wants 15.4, which rounds up to a 16. A 14 inch flex carrying 800 CFM runs about 0.13 of friction. If your wheel only has a sheet metal scale, use the flex duct calculator or the flex duct CFM chart for flex runs.

Then there's the habit of using the same friction rate on every job. 0.08 and 0.10 are common starting points for residential branches, but neither is a rule. A long run with a lot of fittings and a filter that eats static can need a lower number. Work it out from the blower data each time.

Why the online answer and the wheel differ a little

A slide rule is a printed chart that you read by eye, and the marks between sizes are close together. The calculator solves the friction equation directly (Darcy-Weisbach with the Colebrook friction factor, 0.0005 ft roughness for galvanized, standard air). Expect the two to disagree by a few percent. Results can differ from another chart or the manufacturer's data by 5 percent or more. If the two answers straddle a stock size, take the bigger one, or check the actual friction at both sizes before you choose.

Both assume standard air, about 70 °F at sea level. And both size one duct at a time. For the whole system, ACCA Manual D governs, along with the equipment data and local code.

Frequently asked questions

What friction rate should I set on a ductulator?

Work it out from the job: available static pressure for the ducts times 100, divided by the total effective length of the longest run. Many residential branch runs end up somewhere around 0.08 to 0.10 in. w.g. per 100 ft, but that's a rule of thumb, and a Manual D report overrides it.

Is there an online ductulator?

Yes. The duct size calculator on this site does the same job as the wheel. Enter the CFM and a friction rate or target velocity, and it shows the exact and stock round size, the velocity and the equal-friction rectangular sizes for 4 to 14 inch heights. It's free and works on a phone.

How do I convert round to rectangular on a ductulator?

Use the rectangular scale on the back, which matches sizes by equal friction, not equal area. For 800 CFM at 0.08 that gives about 8 x 20 or 10 x 15 for a 13.2 inch round. Matching area alone would give an 8 x 18, which runs about 16 percent over the design friction rate.

Can I use a ductulator for flex duct?

Only if it has a flex scale. The galvanized side reads too small for flex, and compression makes it worse. At 800 CFM and 0.08, flex at 4% compression needs about 15.4 inches, against 13.2 for galvanized.